PRODUCT SHOW
Self-supporting LV-ABC lines according to HD 626(German standard)
Self-supporting LV-ABC Cables
according to HD 626 S1:1996 Part 4-Section F
Aluminium conductors with XLPE insulation, included in national products/standard:
NFA2X(VDE 0276-626 4F-1), AsXS(n)(PL WT92/K396) 1-AES(CSN 34761-4F)
Physical Data
Cross section (mm2) |
Conductor diameter | Thickness of insulation | Core diameter max (mm) |
Current carrying capacity(A*) |
Breaking load (kN) |
||
Min.(mm) | Max.(mm) | Nom.(mm) | Min.(mm) | ||||
16 | 4.6 | 5.1 | 1.2 | 1.00 | 7.8 | - | 2.60 |
25 | 5.8 | 6.5 | 1.3 | 1.07 | 10.0 | 107 | 4.17 |
35 | 6.8 | 7.5 | 1.3 | 1.07 | 11.0 | 132 | 5.78 |
50 | 7.9 | 8.6 | 1.5 | 1.25 | 12.5 | 165 | 8.45 |
70 | 9.7 | 10.2 | 1.5 | 1.25 | 14.0 | 205 | 11.32 |
95 | 11.0 | 12.0 | 1.7 | 1.50 | 16.1 | - | 15.30 |
120 | 12.0 | 13.5 | 1.8 | 1.60 | 17.6 | - | 20.00 |
150 | 13.9 | 15.0 | 1.8 | 1.60 | 18.8 | - | 25.00 |
* Defined for ambient temperature of 35 and max. Conductor temperature of 80¡æ
Dimensions of cable bundle
Number of cores x cross section+public lighting conductors(mm2) | Bundle diameter approx.(mm) |
2x16 | 15 |
2x25 | 18 |
2x35 | 20 |
4x16 | 18 |
4x25 | 22 |
4x35 | 25 |
4x50 | 28 |
4x70 | 32 |
7x70+1x35 | 36 |
4x70+2x35 | 40 |
4x95 | 37 |
4x120 | 40 |
4x120+2x35 | 43 |
4x150 | 44 |