PRODUCT SHOW

Self-supporting LV-ABC cables(Franch srandard)

Self-supporting LV-ABC Cables
according to HD 626 S1:1996 Part 6-Section E
Aluminium conductors with XLPE insulation, included in national products/standards:
NFC33-209
Dimensions of conductors

Cross section
(mm2)
Conductor diameter Thickness of insulation Core diameter Current
carrying
capacity(A*)
Breaking
load
(kN)
Min.(mm) Max.(mm) Nom.(mm) Min.(mm) Min.(mm) Max.(mm)
16 4.6 5.1 1.2 - 7.0 7.8 - -
25 5.8 6.3 1.4 - 8.6 9.4 112 -
35 6.8 7.3 1.6 - 10.0 10.9 138 -
50 7.9 8.4 1.6 - 11.1 12.0 168 -
70 9.7 10.2 1.8 - 13.3 14.2 213 -
95 11.0 12.0 1.8 - 14.6 15.7 258 -
120 12.0 13.1 1.8 - 15.6 16.7 306 -
150 13.9 15.0 1.7 - 17.3 18.6 344 -


* Defined for ambient temperature of 35 and max. Conductor temperature of 80¡æ
Dimensions of cable bundle
Cross section
(mm2)
Conductor diameter Thickness of insulation Core diameter Current
carrying
capacity(A*)
Breaking
load
(kN)
Min.(mm) Max.(mm) Nom.(mm) Min.(mm) Min.(mm) Max.(mm)
54.6 9.2 9.6 1.6 - 12.3 13.0 - 16.6
70 10.0 10.2 1.5 - 12.9 13.6 - 20.5
95 12.2 12.9 1.6 - 15.3 16.3 - 27.5


Dimensions of bundle cable
Number of phzse cores x cross section+public lighting conductors+neutral cross section(mm2) Bundle diameter approx.(mm)
3x25mm2+54.6mm2 15
3x35mm2+kX16mm2+54.6mm2 18
3x50mm2+kX16mm2+54.6mm2 20
3x70mm2+kX16mm2+54.6mm2 18
3x70mm2+kX25mm2+54.6mm2 22
3x70mm2+kX16mm2+70mm2 25
3x95mm2+kX16mm2+70mm2 28
3x120mm2+kX16mm2+70mm2 32
3x120mm2+kX16mm2+95mm2 36
3x150mm2+kX16mm2+70mm2 40
3x150mm2+kX16mm2+95mm2 37