PRODUCT SHOW
Dimensions of LV-ABC line according to HD 626(Finland standard)
LV-ABC lines with bare neutral messenger
according to HD 626 S1:1996 Part 5-Section D
Plase conductors with XLPE Insulation, included in
national products/standards:AMKA(SFS 2200)
Dimensions of conductors
Cross section (mm2) |
Conductor diameter | Thickness of insulation | Core diameter | Current carrying capacity(A*) |
Breaking load (kN) |
|||
Min.(mm) | Max.(mm) | Nom.(mm) | Min.(mm) | Min.(mm) | Max.(mm) | |||
16 | 4.4 | ¡À0.05 | 1.4 | - | 7.1 | 7.3 | 70 | - |
25 | 5.9 | ¡À0.20 | 1.4 | - | 8.3 | 9.1 | 95 | - |
35 | 6.9 | ¡À0.20 | 1.6 | - | 9.7 | 10.5 | 115 | - |
50 | 8.1 | ¡À0.25 | 1.6 | - | 10.8 | 11.8 | 140 | - |
70 | 9.7 | ¡À0.25 | 1.8 | - | 12.8 | 13.8 | 180 | - |
120 | 12.8 | ¡À0.30 | 2.0 | - | 16.2 | 17.4 | 250 | - |
* Defined for ambient temperature of 35 and max. Conductor temperature of 80¡æ
Dimensions of cable bundle
Cross section (mm2) |
Conductor diameter | Thickness of insulation | Core diameter | Current carrying capacity(A*) |
Breaking load (kN) |
|||
Min.(mm) | Max.(mm) | Nom.(mm) | Min.(mm) | Min.(mm) | Max.(mm) | |||
25 | 5.9 | ¡À0.20 | - | - | 5.5 | 6.3 | - | 7.4 |
35 | 6.9 | ¡À0.20 | - | - | 6.5 | 7.3 | - | 10.3 |
50 | 8.1 | ¡À0.25 | - | - | 7.6 | 8.6 | - | 14.2 |
70 | 7.9 | ¡À0.25 | - | - | 9.2 | 10.2 | - | 20.6 |
95 | 11.4 | ¡À0.30 | - | - | 10.8 | 12.0 | - | 27.9 |
Dimensions of bundle cable
Number of Phase Core x cross section + neutral cross section(mm2) | Bundle diameter approx.(mm) |
1x16+25 | 15 |
3x16+25 | 22 |
4x16+25 | 22 |
3x25+35 | 26 |
4x25+35 | 26 |
3x35+50 | 30 |
3x50+70 | 35 |
3x70+95 | 41 |
3x120+95 | 47 |