PRODUCT SHOW

S9 series 33kv distribution transformer

50kVA~1600kVA 3-phase Duplex Winding Non-excited Tap-Changing Distribution Transformer

Rated
capacity
(kVA)
Voltage Combination
and Tap range
Vector
Group
Symbol
No-load
loss
(kw)
Load
loss
(kw)
No-load
current
(%)
Short-circult
Impedance
Voltage
%
HV
(kV)

HV Tap
Range%
LV
(kV)
50 35 ±5
±2×2.5
0.4 Dyn11
Yyn0
0.21 0.27/1.21 2.00 6.5
100 0.29 2.12/2.02 1.80
125 0.34 2.50/2.38 1.70
160 0.36 2.97/2.83 1.60
200 0.43 3.50/3.33 1.50
250 0.51 4.16/3.96 1.40
315 0.61 5.01/4.77 1.40
400 0.73 6.05/5.76 1.30
500 0.86 7.28/6.93 1.20
630 1.04 8.28 1.10
800 1.23 9.90 1.00
1000 1.44 12.15 1.00
1250 1.76 14.67 0.90
1600 2.12 17.55 0.80

Note 1: Rated capacity 500KVA and below transformer, the load loss above the oblique line in the table applies to Dyn 11 or Yzn11;the load loss
below the oblique line applies to Yyno. Note 2: According to requirements, the transformer can supply HV tap change 2 2.5 %
Note 3: outline dimension is designed according to requirements.

630kVA~31500kVA 3-phase Duplex Winding Non-excited Tap-Changing Power Transformer
Rated
capacity
(kVA)
Voltage Combination
and Tap range
Vector
Group
Symbol
No-load
loss
(kw)
Load
loss
(kw)
No-load
current
(%)
Short-circult
Impedance
Voltage
%
HV
(kV)

HV Tap
Range%
LV
(kV)
630 35 ±5
±2×2.5
3.15
6.3
10.5
Yd11 1.04 8.28 1.10 6.5
800 1.23 9.90 1.00
1000 1.44 12.15 1.00
1250 1.76 14.67 0.90
1600 2.12 17.55 0.80
2000 2.71 19.35 0.70
2500 3.20 20.70 0.60
3150 35-38.5 ±5
±2×2.5
3.15
6.3
10.5
3.80 24.30 0.56 7.0
4000 4.52 28.80 0.56
5000 5.40 33.03 0.48
6300 6.56 36.90 0.48 7.5
8000 35-38.2 ±5
±2×2.5
3.15
3.3
6.3
6.6
10.5
11
Ynd11 9.00 40.50 0.42
10000 10.88 47.70 0.42
12500 12.60 56.70 0.40 8.0
16000 15.20 69.30 0.40
20000 18.00 83.70 0.40
25000 21.28 99.00 0.32
31500 25.28 118.80 0.32